Apraksts
SPECIFICATIONS
Insulation Test 4101 IN
Test voltage (DC V) 250V / 500V / 1000V
Output voltage @ 1mA Rated test Voltage +10% Max
Measuring ranges 0.2M~2G / 0.2M-4G / 0.2M-8GΩ
Accuracy 0.2M~4GΩ : ±3%rdg
4GΩ~8GΩ : ±5%rdg
When voltage is constant,
Current is limited at 1.2mA
Short circuit current 4mA Max.
Continuity Test
Measuring ranges 0.01-1999Ω
Accuracy
0.01-100Ω : ±1.0%rdg
100-300Ω : ±1.5%rdg
300-1999Ω : ±2.0%rdg
Short circuit current >220mA
Open circuit voltage 5V dc
Resolution ±2 counts
Voltmeter
AC voltage (Auto) 0-700V
DC voltage (Auto) 0-950V
Accuracy ±1.5% rdg
Resolution ±1V
Protections
Over load 700V (between all terminals)
Over voltage Class III-700V towards ground
Fuse 500mA 250V, (5 × 20mm), HBC, Fast Blow
General
Display 2 lines × 16 characters LCD
Auto-null threshold 5Ω
Buzzer threshold 3Ω
Fast test 10Sec
Long test 60Sec
With PI and DAR test function 10Min
Load battery test current About 300mA
Operating temperature 0°C to 40°C not in full sun
Storage temperature -10°C to 50°C
Dimensions 250(L) × 190(W) × 110(D)mm
Weight (battery included) Approx 1460g.
Power source 1.5V(AA) × 8
Safety standard EN 61010-1 CAT III 600V
EN 61326-1
Accessories:
Instruction manual
Test leads
Shoulder belt
Batteries