Apraksts
SPECIFICATIONS
Measuring ranges
0-200.0mΩ in steps of 100μΩ
0-2000mΩ in steps of 1mΩ
0-20.00Ω in steps of 10mΩ
0-200.0Ω in steps of 100mΩ
0-2000Ω in steps of 1Ω
Accuracy
±0.5% of reading ±2digits over the
operating temperature range,
-15ºC ~ 55ºC, with the supplied
test leads
Test current
1mA=>2000Ω range
10mA=>200Ω and 20Ω ranges
100mA=>2000mΩ and 200mΩ ranges
Test current
accuracy
±0.1%
Protection fuses
Mains = 500mA / 250V, 5 × 20mm fast blow
Current = 500mA / 250V, 5 × 20mm fast blow
Voltage = 500mA / 250V, 5 × 20mm fast blow
Maximum output
voltage (C1~C2) 20V
Dimensions 250(L) × 190(W) × 110(D)mm
Weight 4136 mO: 1530g
4137 mO: 1500g
Safety standard EN 61010-1 CAT IV 20V
EN 61326-1
Accessories:
Instruction manual Test leads
Shoulder belt
Batteries 1.5V(AA) × 8 (4137 mO)