Apraksts
SPECIFICATIONS
Loop Impedance
Range Measuring
range
Nominal test
current at 0 Ω
external loop
Accuracy
20 Ω 0.00~19.99 Ω 23A / 40ms
200 Ω 0.0~199.9 Ω 2.3A / 40ms (2%rdg + 4dgt)
2000 Ω 0~1999 Ω 15mA / 400ms
Prospective Short-circuit Current
Range Measuring
range
Nominal test
current at 0 Ω
external loop
Accuracy
20 KA 0.00~4.00 KA 23A / 40ms Consider
accuracy
of loop
impedance
2000 A 0~1999 A 23A / 40ms
200 A 0.0~199.9 A 2.3A / 40ms
General
Temperature 0 ~ 40 °C
System voltage 230V
+13%
-15%
System frequency 50Hz
None Battery
system voltage 150V ~ 260V
Over Temperature
Protection
When overheating,the ” ” symbol
will show on the LCD, and the 8025LP
stop measuring.
Wiring check
P-E LEDs illuminate when the
wiring polarity of circuit under
P-N test is correct
N-E
LED is light when P and N are
reversed or the Earth is not
connected.
15mA Loop
measurement
Loop impedance 2000Ω range
measurement is carried out with low
test current (15mA).
The current will not cause tripping
out for ELCBs.